PREVENTION OF DISTRIBUTION TRANSFORMER PREMATURE FAILURES

Journal: International Journal of Engineering Sciences & Research Technology (IJESRT) (Vol.6, No. 5)

Publication Date:

Authors : ; ;

Page : 289-295

Keywords : Furan derivatives; Harmonics; Transformers insulation; Moderately deteriorated; Extensively deteriorated.;

Source : Downloadexternal Find it from : Google Scholarexternal

Abstract

This paper deals with three types of Distribution Transformer failure analysis tests which can help in monitoring the Distribution Transformers condition. The three methods are Conventional oil test, Furan derivatives test, and Markov models criteria. Conventional oil testing procedures determine the gas concentrations in the Distribution Transformers oil sample and analyzing the defect by considering the ratio of two suitable gasses. Furan derivative analysis includes determination of Furan derivatives present in the Distribution Transformers oil sample and helps in deciding the Distribution Transformers insulation condition. A computer program was developed for the Hidden Markov model, which helps in finding out the fault probability of the Distribution Transformer. Here, we demonstrate the application of these three methods on a 132/33kV, 15MVA Distribution Transformer from CSEB substation, Korba Bilaspur, India, under three different conditions namely healthy, moderately deteriorated and extensively deteriorated conditions and results obtained.