EXPERIMENTAL STUDY TO THE PERFORMANCE OF THE DISPLACEMENT VENTILATION UNDER DIFFERENT OPERATION CONDITIONS
Journal: International Journal of Advanced Research (Vol.6, No. 6)Publication Date: 2018-07-25
Authors : Israa Ali AbdulGhafor Adnan. A. Abdulrasool; Qasem S. Mehdi.;
Page : 485-494
Keywords : Displacement Ventialtion Thermal Conditions.;
Abstract
The present study presents the experimental study of performance of the displacement ventilation . The experimental study included the effect of different internal loads of (1600,1300and 1000)W , different supplied air temperatures of ( 18,20,22and 24)?C and different supplied air velocities (0.75,1,1.25 and 1.45)m/s on the performance of displacement ventilation . The experimental results show that the cooling capacity of air increases as the temperature of supplied air decreases. At a increases in temperature of supplied air by (33.33)%,the cooling capacity of air decreases by (23.52, 24.05 and 20.63)% for internal load of (1600,1300 and 1000 )W respectively .While as supplied air velocity increases ,the cooling capacity of air increases .At supplied air increases by (93.33)% ,the cooling capacity increase by (33.61, 39.23 and 36.8 )% for internal load of (1600, 1300 and 1000)W respectively.
Other Latest Articles
- Isolation and Identification Methods for Slackia Exigua and Investigation of the Relationship between this Organism and Peri-Implantitis
- A Study of Role of Gender in High on Treatment Platelet Reactivity (HRPR) on outcome in Patients Undergoing Percutaneous Coronary Intervention
- Comprehensive Approach in “Liver Clot” Management Case Report
- ACTIVATING NEWS POWER: A CASE STUDY ON THE SYRIAN ELECTION NEWS COVERAGE
- Synaptic-Adhesion Molecules Neurexin 1 and Neuroligin 1 as Novel Prognostic Factors in Oral Squamous Cell Carcinoma
Last modified: 2018-07-25 19:24:21