DETERMINATION OF THE EFFECTIVENESS OF HARMONIC FILTERS IN THE 10 KV NETWORK OF THE METALLURGICAL PLANT
Journal: Collection of scholarly papers of Dniprovsk State Technical University (Technical Sciences) (Vol.1, No. 30)Publication Date: 2017-08-29
Authors : E. D. Khmel'nitsky O. V. Kluyev;
Page : 104-111
Keywords : parameters of power filter; the third harmonic; the structure of filter-compensating device;
Abstract
The paper deals with the analysis of work of filter-compensating device (FCD), installed in substations of 10 kV steel plant. Calculations on the efficiency of harmonic filters (f-3, f-5, f-7, f-11) are performed. Determined by the low efficiency of the filter of the 3rd harmonic, if it is indicated that an invalid combination of include filters f-3,
f-7, f-11. The proposed changes in the structure of the device of FCD with filter replacement f-11 to a capacitor without protective reactor.