The calculation of required fire resistance limits for engineering structures of technological pipe racks at oil and gas processing plants on the basis of an evaluation of the time needed for personnel evacuation and rescue in case of fire
Journal: Pozharovzryvobezopastnost/Fire and Explosion Safety (Vol.30, No. 5)Publication Date: 2021-10-30
Authors : A. Yu. Shebeko Yu. N. Shebeko A. V. Zuban;
Page : 58-65
Keywords : reliability of building structures; probabilistic approach; evacuation and rescue time; dispersion of the fire resistance limit; fire resistance;
Abstract
Introduction. GOST R 12.3.047-2012 standard offers a methodology for determination of required fire resistance limits of engineering structures. This methodology is based on a comparison of values of the fire resistance limit and the equivalent fire duration. However, in practice incidents occur when, in absence of regulatory fire resistance requirements, a facility owner, who has relaxed the fire resistance requirements prescribed by GOST R 12.3.047–2012, is ready to accept its potential loss in fire for economic reasons. In this case, one can apply the probability of safe evacuation and rescue to compare distributions of fire resistance limits, on the one hand, and evacuation and rescue time, on the other hand. A methodology for the identification of required fire resistance limits. The probabilistic method for the identification of required fire resistance limits, published in work [1], was tested in this study. This method differs from the one specified in GOST R 12.3.047-2012. The method is based on a comparison of distributions of such random values, as the estimated time of evacuation or rescue in case of fire at a production facility and fire resistance limits for engineering structures. Calculations of required fire resistance limits. This article presents a case of application of the proposed method to the rescue of people using the results of full-scale experiments, involving a real pipe rack at a gas processing plant [2]. Conclusions. The required fire resistance limits for pipe rack structures of a gas processing plant were identified. The calculations took account of the time needed to evacuate and rescue the personnel, as well as the pre-set reliability of structures, given that the personnel evacuation and rescue time in case of fire is identified in an experiment.
Other Latest Articles
- A model of response efficiency in the hierarchical control system based on the assessment of readiness of fire departments
- Flameless combustion of wood: charring and heat release characteristics
- A change in the air temperature inside a 20-liter chamber when air is added from the receiver
- A comparative analysis of the requirements of Russia and the United States to the fire resistance of building structures of oil refineries and petrochemical plants
- The expediency of using fire retardant cable coatings