Analysis of Deterioration Characteristics by Filtering Processes at 6.6kV Power Cable Systems in Operation
Journal: The Journal of the Institute of Internet, Broadcasting and Communication (Vol.14, No. 4)Publication Date: 2014-08-31
Authors : Kee-Hong Um; Kwan-Woo Lee;
Page : 205-211
Keywords : XLPE; Loss tangent; Insulation resistance; Power cables; Filtering;
Abstract
With a development of modern industry, demand for electric power is rapidly increasing and the capacity of power transfer is required to become bigger and bigger. At power station, the high-voltage power cable is used as the only method in order to transfer electric power. In this paper, we have analyzed the deterioration characteristics of 6.6kV power cable systems in operation. For the time duration of 2000 days, we have measured the cable in operation in order to extract the data for the deterioration characteristics. By analyzing the data by means of several steps of filtering processes, we could obtain the linear relations of insulation resistances as a function of time. Furthermore, we can verify that the progress characteristics in deterioration process of 6.6kV power cable systems follows the process of heat deterioration.
Other Latest Articles
- Developing Equipment to Detect the Deterioration Status of 6.6kV Power Cables in Operation at Power Station
- Performance Evaluation of MissLess Soft Keyboard with Recommendation
- Design of Knowledge Management System based on SNS
- A Feature Point Tracking Method By Using Template Matching and Buffer
- Vehicle Behavior Characteristics According to the Change of Vehicle Speed and Road Vertical Grades
Last modified: 2016-01-20 14:51:16