Critical Points of Simplified Model for Ferroresonance Phenomenon in Single Phase Power Transformers
Journal: International Research Journal of Advanced Engineering and Science (Vol.1, No. 2)Publication Date: 2016-05-11
Authors : Radwan M. Al-Bouthigy;
Page : 44-49
Keywords : Single?phase power transformers; modeling; ferroresonance; overvoltage’s; overcurrent’s; simulated annealing technique; critical points;
Abstract
This paper is aimed at proposing a simplified model of ferroresonance phenomenon in single?phase power transformers. The transformer is modelled and the non?linear equivalent resistance and inductance of the magnetizing branch are determined from open?circuit test. The ferroresonance resulting from energizing the transformer through a series capacitor is assessed and the calculated primary voltage and current values are compared with those measured experimentally. A robust meta-heurtics optimization technique, Simulated Annealing, is applied in this paper for determining for ferroresonance jump up and jump down critical points. The calculated values agreed reasonably with those measured experimentally with a deviation not exceeding 7%.
Other Latest Articles
- Forensic Spoofer Location Detection Using Passive IP Traceback Techniques
- Design and Implementation of Dynamic Voltage Restorer for Voltage Sag Mitigation
- Automatic Itinerary Planning for Traveling Service Based on Budget using Spatial Datamining with Hadoop
- Selection of Capacitance for Compensated Self Excited Induction Generator Using Meta-Heuristic Approach
- Book Review, Gottfried Hagen, Bir Osmanlı Coğrafyacısı İş Başında, Kâtib Çelebi'nin Cihannümâ'sı ve Düşünce Dünyası