PERSPECTIVE OF USE OF GAS-EXTINGUISHING PLANT ON THE BASE OF CARBON DIOXIDE FOR FIRE EXTINGUISHING ON ELECTROENERGETICS FACILITIES
Journal: Pozharovzryvobezopastnost/Fire and Explosion Safety (Vol.22, No. 11)Publication Date: 2013-11-28
Authors : ALESHKOV M. V. Candidate of Technical Sciences KUZMENKO K. P. Candidate of Technical Sciences INCHIKOV V. P. Head of Project Office;
Page : 43-48
Keywords : electroenergetics; carbon dioxide; automatic extinguishing plant; fire safety;
- PERSPECTIVE OF USE OF GAS-EXTINGUISHING PLANT ON THE BASE OF CARBON DIOXIDE FOR FIRE EXTINGUISHING ON ELECTROENERGETICS FACILITIES
- CARBON DIOXIDE EXTINGUISHING OF FIRE IN VERTICAL STEEL TANKS WITH OIL AND OIL PRODUCTS
- Actual problems of navigation to the fire robotic trunks in robotic fire extinguishing system. Part 2. RFM operating programs for fire extinguishing with static streams considering RFMs positioning to fire area
- An experimental study of the fire extinguishing ability of modular fire extinguishing installations if astralene-modified water mist is used
- Extinguishing production buildings by using “dry water” (novek 1230) in automatic fire extinguishing installations
Abstract
Present article shows that use of gas-extinguishing plants (GEP) with carbon dioxide (CO2) as gas extinguishing agent is most perspective for fire protection of electroenergetics facilities. Problems of use of GEP on the base of MIZhU for fire protection of electroenergetics facilities are touched, particularly, for power facilities' safety on open space. It is shown that discharging time of carbon dioxide, calculated with existing hydraulic calculation method, differs from natural tests' results. Based on experimental data, it is determined that effectiveness of local by volume fire extinguishing method mostly depends on computational accuracy of discharging time of carbon dioxide. Accentuated declarative type of lag's conception for gas-extinguishing plant. Proposal to amend regulations, concerning conception “lag” with regard to gas extinguishing plant, are stated.
Other Latest Articles
- HISTORY AND PERSPECTIVES FOR DEVELOPMENT FIRE MACHINES AT MILITARY CATERPILLAR AND WHEEL CHASSIS
- KINETIC AND GAZDYNAMIC REASONS OF ACCIDENTAL EXPLOSIONS OF HYDROGEN
- SYNTHESIS OF THE ADAPTIVE CONTROL ALGORITHM LIQUIDATION OF FOREST FIRES
- EFFECT OF STRUCTURE OF THE MOLECULE ON PARAMETERS OF FIRE HAZARD OF NITROGEN-CONTAINING ORGANIC SUBSTANCES
- WOOD HEATED TO HIGH TEMPERATURES PARTICLES FORMATION AS A RESULT OF GROUND LIGHTNING DISCHARGE INFLUENCE ON CONIFEROUS TREE TRUNK
Last modified: 2019-10-24 18:53:41