Continuous Wavelet Transform (CWT) based Analysis of Very Fast Transient over Voltages of 132 KV Power Transformer
Journal: International Journal of Computational Engineering Research(IJCER) (Vol.05, No. 02)Publication Date: 2015-02-01
Authors : K.Prakasam; D.Prabhavathi; Dr.M.Suryakalavathi; Dr.B.Ravindranath Reddy;
Page : 01-07
Keywords : disconnect or; High voltage level; MAT LAB; Switching; Switching operations; Travelling Very Fast Transient over voltages; Wavelet transform;
Abstract
This paper results the most accurate results of Very Fast Transient over Voltages of 132 KV transformer caused by the switching operation. A 132KV transformer is designed using MATLAB simulin, the VFTOs generated by the switching operations have been analyzed and are presented. The VFTOs generated due to Disconnector switching operation can cause insulation failure at very high voltage levels. The reasons of these problems are travelling waves which is generated during switching operations in a gas-insulated substation (GIS). Calculation of Very Fast Transient Over voltage has been carried out using MATLAB 7.8 for various switching.